2 meaning of the diagnosis values, Operation 123 – Siemens SIPART PS2 6DR52xx User Manual
Page 123
Operation
123
SIPART PS2 Manual
A5E00074631--06
No.
Reset
possible
Unit
Values than
can be
indicated
Meaning
Abbre-
viation
21
P100
Potentiometer value upper stop (100%)
0.0 to 100.0
%
22
IMPUP
Pulse length up (Impulse Length Up)
2 to 160
ms
23
IMPDN
Pulse length down (Impulse Length Down)
2 to 160
ms
24
DBUP
Dead zone up (Dead Band Up)
0.1 to 10.0
%
25
DBDN
Dead zone down (Dead Band Down)
0.1 to 10.0
%
26
SSUP
Short step zone up (Short Step Zone Up)
0.1 to 100.0
%
27
SSDN
Short step zone down (Short Step Zone Down)
0.1 to 100.0
%
28
TEMP
Current temperature
--40 to 85
_
C
29
TMIN
Minimumtemperature (“min/max pointer”)
--40 to 85
_
C
30
TMAX
Maximumtemperature (“min/max pointer”)
--40 to 85
_
C
31
T1
Number of operating hours in temperature range 1
0 to 4.29E9
hours
32
T2
Number of operating hours in temperature range 2
0 to 4.29E9
hours
33
T3
Number of operating hours in temperature range 3
0 to 4.29E9
hours
34
T4
Number of operating hours in temperature range 4
0 to 4.29E9
hours
35
T5
Number of operating hours in temperature range 5
0 to 4.29E9
hours
36
T6
Number of operating hours in temperature range 6
0 to 4.29E9
hours
37
T7
Number of operating hours in temperature range 7
0 to 4.29E9
hours
38
T8
Number of operating hours in temperature range 8
0 to 4.29E9
hours
39
T9
Number of operating hours in temperature range 9
0 to 4.29E9
hours
40
VENT1
Number of switching operations pilotvallve 1
0 to 4.29E9
--
41
VENT2
Number of switching operations pilotvallve 2
0 to 4.29E9
--
42
STORE
Save current values as “last maintenance”
(press increment button for 5s) (Store)
--
--
43
PRUP
Prediction up
1 to 40
--
44
PRDN
Prediction down
1 to 40
--
45
WT00
Number of operating hours in actuating range WT00
0 to 4.29E9
hours
x
46
WT05
Number of operating hours in actuating range WT05
0 to 4.29E9
hours
x
47
WT10
Number of operating hours in actuating range WT10
0 to 4.29E9
hours
x
48
WT30
Number of operating hours in actuating range WT30
0 to 4.29E9
hours
x
49
WT50
Number of operating hours in actuating range WT50
0 to 4.29E9
hours
x
50
WT70
Number of operating hours in actuating range WT70
0 to 4.29E9
hours
x
51
WT90
Number of operating hours in actuating range WT90
0 to 4.29E9
hours
x
52
WT95
Number of operating hours in actuating range WT95
0 to 4.29E9
hours
x
53
mA
Setpoint current
0.0 to 20.0
mA
Table 4-1
Overview of diagnosis values
4.5.2 Meaning of the diagnosis values
Number of strokes
During operation, the actuator movements are added up and can be
read off here as the number of strokes. Unit: 100% strokes, i.e. the
path between 0 and 100 % and back. The value is written into a
non-volatile memory every 15 minutes. It can be set to zero with the
increment button
.
Number of changes of direction
1 STRKS
2 CHDIR