beautypg.com

2 meaning of the diagnosis values, Operation 123 – Siemens SIPART PS2 6DR52xx User Manual

Page 123

background image

Operation

123

SIPART PS2 Manual

A5E00074631--06

No.

Reset

possible

Unit

Values than

can be

indicated

Meaning

Abbre-

viation

21

P100

Potentiometer value upper stop (100%)

0.0 to 100.0

%

22

IMPUP

Pulse length up (Impulse Length Up)

2 to 160

ms

23

IMPDN

Pulse length down (Impulse Length Down)

2 to 160

ms

24

DBUP

Dead zone up (Dead Band Up)

0.1 to 10.0

%

25

DBDN

Dead zone down (Dead Band Down)

0.1 to 10.0

%

26

SSUP

Short step zone up (Short Step Zone Up)

0.1 to 100.0

%

27

SSDN

Short step zone down (Short Step Zone Down)

0.1 to 100.0

%

28

TEMP

Current temperature

--40 to 85

_

C

29

TMIN

Minimumtemperature (“min/max pointer”)

--40 to 85

_

C

30

TMAX

Maximumtemperature (“min/max pointer”)

--40 to 85

_

C

31

T1

Number of operating hours in temperature range 1

0 to 4.29E9

hours

32

T2

Number of operating hours in temperature range 2

0 to 4.29E9

hours

33

T3

Number of operating hours in temperature range 3

0 to 4.29E9

hours

34

T4

Number of operating hours in temperature range 4

0 to 4.29E9

hours

35

T5

Number of operating hours in temperature range 5

0 to 4.29E9

hours

36

T6

Number of operating hours in temperature range 6

0 to 4.29E9

hours

37

T7

Number of operating hours in temperature range 7

0 to 4.29E9

hours

38

T8

Number of operating hours in temperature range 8

0 to 4.29E9

hours

39

T9

Number of operating hours in temperature range 9

0 to 4.29E9

hours

40

VENT1

Number of switching operations pilotvallve 1

0 to 4.29E9

--

41

VENT2

Number of switching operations pilotvallve 2

0 to 4.29E9

--

42

STORE

Save current values as “last maintenance”

(press increment button for 5s) (Store)

--

--

43

PRUP

Prediction up

1 to 40

--

44

PRDN

Prediction down

1 to 40

--

45

WT00

Number of operating hours in actuating range WT00

0 to 4.29E9

hours

x

46

WT05

Number of operating hours in actuating range WT05

0 to 4.29E9

hours

x

47

WT10

Number of operating hours in actuating range WT10

0 to 4.29E9

hours

x

48

WT30

Number of operating hours in actuating range WT30

0 to 4.29E9

hours

x

49

WT50

Number of operating hours in actuating range WT50

0 to 4.29E9

hours

x

50

WT70

Number of operating hours in actuating range WT70

0 to 4.29E9

hours

x

51

WT90

Number of operating hours in actuating range WT90

0 to 4.29E9

hours

x

52

WT95

Number of operating hours in actuating range WT95

0 to 4.29E9

hours

x

53

mA

Setpoint current

0.0 to 20.0

mA

Table 4-1

Overview of diagnosis values

4.5.2 Meaning of the diagnosis values

Number of strokes
During operation, the actuator movements are added up and can be

read off here as the number of strokes. Unit: 100% strokes, i.e. the

path between 0 and 100 % and back. The value is written into a

non-volatile memory every 15 minutes. It can be set to zero with the
increment button

.

Number of changes of direction

1 STRKS

2 CHDIR

This manual is related to the following products: