beautypg.com

Operation 102, Linear (12.sfct = lin, factory setting) – Siemens SIPART PS2 6DR52xx User Manual

Page 102

background image

Operation

102

SIPART PS2 Manual

A5E00074631--06

Six valve characteristics are stored in the positioner

S

linear

(12.SFCT = Lin, factory setting)

S

equal percentage

1 : 25

(12.SFCT = 1:25)

S

equal percentage

1 : 33

(12.SFCT = 1:33)

S

equal percentage

1 : 50

(12.SFCT = 1:50)

S

inverse equal percentage

25 : 1

(12.SFCT = n1:25)

S

inverse equal percentage

33 : 1

(12.SFCT = n1:33)

S

inverse equal percentage

50 : 1

(12.SFCT = n1:50)

S

freely adjustable

(12.SFCT = FrEE)

Setpoint turning points
A flow parameter can be assigned to the respective setpoint turning

value at an interval of 5 %. These points lead to a polygon chain with

20 straight lines which therefore represents a projection of the valve

characteristic.

w

x

10

20

30

40

50

60

70

80

90

100%

10

0

0

20

30

40

50

60

70

80

90

100 %

9 SFCT = Lin

Modul

ati

on

range

w

x

10

20

30

40

50

60

70

80

90

100%

10

0

0

20

30

40

50

60

70

80

90

100 %

2

10

6

14

19

4

12

17

8

16

1

9

5

13

18

3

11

7

15

20

SL 0

12 SFCT = FrEE

L

imit for tight closing

Example:

39 YCLS = UP
41 YCUP = 85.0

L

imit for tight closing

Example:

39 YCLS = UP
41YCUP = 75.0

L

imit for tight closing

Example:

39 YCLS = DO
40YCDO = 10.0

L

imit for tight closing

Example:

39 YCLS = DO
40 YCDO = 15.0

Setpoint turning point
Example:

18 SL5 = 45.0

Modul

ati

on

range

Setpoint

Setpoint

Figure 4-9

Setpoint characteristic, manipulated variable standardization and tight closing function

The setpoint vertex values can only be input at 12.SFCT=FrEE. You

may only enter a strictly monotonous characteristic, and two consecu-

tive vertex values must differ by at least 0.2 %.

13.SL0 to 33.SL20

This manual is related to the following products: