Operation 102, Linear (12.sfct = lin, factory setting) – Siemens SIPART PS2 6DR52xx User Manual
Page 102
Operation
102
SIPART PS2 Manual
A5E00074631--06
Six valve characteristics are stored in the positioner
S
linear
(12.SFCT = Lin, factory setting)
S
equal percentage
1 : 25
(12.SFCT = 1:25)
S
equal percentage
1 : 33
(12.SFCT = 1:33)
S
equal percentage
1 : 50
(12.SFCT = 1:50)
S
inverse equal percentage
25 : 1
(12.SFCT = n1:25)
S
inverse equal percentage
33 : 1
(12.SFCT = n1:33)
S
inverse equal percentage
50 : 1
(12.SFCT = n1:50)
S
freely adjustable
(12.SFCT = FrEE)
Setpoint turning points
A flow parameter can be assigned to the respective setpoint turning
value at an interval of 5 %. These points lead to a polygon chain with
20 straight lines which therefore represents a projection of the valve
characteristic.
w
x
10
20
30
40
50
60
70
80
90
100%
10
0
0
20
30
40
50
60
70
80
90
100 %
9 SFCT = Lin
Modul
ati
on
range
w
x
10
20
30
40
50
60
70
80
90
100%
10
0
0
20
30
40
50
60
70
80
90
100 %
2
10
6
14
19
4
12
17
8
16
1
9
5
13
18
3
11
7
15
20
SL 0
12 SFCT = FrEE
L
imit for tight closing
Example:
39 YCLS = UP
41 YCUP = 85.0
L
imit for tight closing
Example:
39 YCLS = UP
41YCUP = 75.0
L
imit for tight closing
Example:
39 YCLS = DO
40YCDO = 10.0
L
imit for tight closing
Example:
39 YCLS = DO
40 YCDO = 15.0
Setpoint turning point
Example:
18 SL5 = 45.0
Modul
ati
on
range
Setpoint
Setpoint
Figure 4-9
Setpoint characteristic, manipulated variable standardization and tight closing function
The setpoint vertex values can only be input at 12.SFCT=FrEE. You
may only enter a strictly monotonous characteristic, and two consecu-
tive vertex values must differ by at least 0.2 %.
13.SL0 to 33.SL20