Operation

121

SIPART PS2 Manual

A5E00074631--06

Time basis for the formation of the average value
Sets the intervals for the formation of the average value. The following

time intervals are available:

30 minutes

8 hours

5 days

60 days

2.5 years

Status of the calculation of the position average
After activating the function with parameter P. PAVG, the initial status

of the calculation of the position average is “IdLE” (inactive). To start

the calculation of the position average, the Greater Than button is

pressed for five seconds. The display text then switches from “IdLE” to

“rEF” (reference average is calculated) and remains there until the

selected time interval has passed. The reference average is then

shown on the display.

.

NOTE
The current comparison average is displayed in the diagnosis menu

under parameter 19.PAVG as soon as the first comparison interval has

passed. During the first comparison interval, “COMP” (comparison

interval) is displayed there.

Threshold 1
First threshold for monitoring the reference average. The factory setting

is 2.0%. If a comparison average deviates from the reference by more

than this value, the threshold 1 error message is triggered.

Threshold 2
Second threshold for monitoring the reference average. The factory

setting is 5.0%. If a comparison average deviates from the reference by

more than this value, the threshold 2 error message is triggered.

Threshold 3
Third threshold for monitoring the reference average. The factory

setting is 10.0%. If a comparison average deviates from the reference

by more than this value, the threshold 3 error message is triggered.

P1.TBASE

P2.STATE

P3.LEVL1

P4.LEVL2

P5.LEVL3