Siemens SIPART PS2 6DR52xx User Manual
Page 121
Operation
121
SIPART PS2 Manual
A5E00074631--06
Time basis for the formation of the average value
Sets the intervals for the formation of the average value. The following
time intervals are available:
30 minutes
8 hours
5 days
60 days
2.5 years
Status of the calculation of the position average
After activating the function with parameter P. PAVG, the initial status
of the calculation of the position average is “IdLE” (inactive). To start
the calculation of the position average, the Greater Than button is
pressed for five seconds. The display text then switches from “IdLE” to
“rEF” (reference average is calculated) and remains there until the
selected time interval has passed. The reference average is then
shown on the display.
.
NOTE
The current comparison average is displayed in the diagnosis menu
under parameter 19.PAVG as soon as the first comparison interval has
passed. During the first comparison interval, “COMP” (comparison
interval) is displayed there.
Threshold 1
First threshold for monitoring the reference average. The factory setting
is 2.0%. If a comparison average deviates from the reference by more
than this value, the threshold 1 error message is triggered.
Threshold 2
Second threshold for monitoring the reference average. The factory
setting is 5.0%. If a comparison average deviates from the reference by
more than this value, the threshold 2 error message is triggered.
Threshold 3
Third threshold for monitoring the reference average. The factory
setting is 10.0%. If a comparison average deviates from the reference
by more than this value, the threshold 3 error message is triggered.
P1.TBASE
P2.STATE
P3.LEVL1
P4.LEVL2
P5.LEVL3