Monitoring of the displacement integral
This parameter activates the monitoring of the displacement integral.

This function allows the preventive maintenance of the control valve,

also see chapter 4.5 “Diagnosics”, page 122.

Limit for the number of strokes
Input of the limit for the number of strokes. The parameter can be used

depending on the requirement profile of the user.
On the one hand, it is possible to enter a maximal number for the

strokes and to use factors smaller than one to receive warning

messages when a certain fraction of the maximal number is reached.

On the other hand, a minimum value can be entered for the strokes.

Factors greater than one are then used to receive warning messages

for certain limits above the minimum value. Factory setting for the limit

is 1 000 000.

Factor 1
Input of the factor for the threshold 1 error message. This factor refers

to the limit for the number of strokes. Factory setting for factor 1 is 1.0.

That means, for L1.LIMIT = 1 000 000 and factor 1 = 1.0, the first

stroke counter error message is triggered after 1 000 000 strokes.

Factor 2
Input of the factor for the threshold 2 error message. This factor refers

to the limit for the number of strokes. Factory setting for factor 2 is 2.0.

That means, for L1.LIMIT = 1 000 000 and factor 2 = 2.0, the second

stroke counter error message is triggered after 2 000 000 strokes.

Factor 3
Input of the factor for the threshold 3 error message. This factor refers

to the limit for the number of strokes. Factory setting for factor 3 is 5.0.

That means, for L1.LIMIT = 1 000 000 and factor 3 = 5.0, the third

stroke counter error message is triggered after 5 000 000 strokes.

L. STRK

L1.LIMIT

L2.FACT1

L3.FACT2

L4.FACT3