Fault indication
(symptoms)
possible cause(s)
Remedies
•
Zero point misadjusts
sporadically (> 3 %).
•
Stress caused by knocks or
shocks result in acceleration
values that are so high that the
friction clutch is misadjusted
(e.g. with “steam pulses” in
steam lines)
•
Eliminate causes of shock
stress.
•
Re-initialize positioner.
•
Complete device function
failure: also no indication in
the display
•
Electrical power supply
insufficient
•
Check electrical power supply.
•
In the event of continuous high
vibration stress (vibrations):
•
Screws on the electrical
connecting terminals can
loosen.
•
Electrical connecting terminals
and/or electronic components
can loosen due to vibrations.
•
Tighten screws and secure
them with locking varnish.
•
Repair (see chapter 5,
page 145)
•
For prevention purposes:
Fit SIPART PS 2 on shock
mounts.
Table 9
4.6 Meaning of the other display text
Remarks on the tables:
nn
stands for variable numerical values
Error symbol
/
(slash): the text segments to the left and right of the-
slash flash alternately
Messages before the installation phase (initial start-up):
Upper lin
e
Lower lin
e
Meaning/cause
Measure
CPU
START
x
x
Message after applying the electrical
power supply
S
Wait
P nnn.n
x
Potentiometer voltage when
positioner is not initialized (P manual
mode) (actual position value in % of
measuring range)
S
Check with the “+” and “--” buttons
whether the entire actuator travel can
be moved along and that “P------” is
never displayed
S
Perform initialization
P------
x
Measuring range exceeded,
potentiometer is in the inactive zone,
switch transmission ratio selector or
effective lever arm have not been
adapted to the actuator travel
S
Switch transmission ratio selector to
90 degrees for part-turn actuators
S
Adjust effective lever length for linear
actuators to measuring range
NOINI
x
Positioner is not initialized
S
Start initialization