Pneumatic leakage
This parameter is used to activate the function for the detection of a

pneumatic leakage. To do so, the changes of position and the internally

used controller output are recorded and filtered, depending on the

direction. The filter result provides a coefficient that allows the detection

of any leakage.
Note that the detection of a leak can only provided clear results for

spring-loaded actuators.

Limit for the leakage indicator
Sets the limit for the leakage indicator The leakage indicator is scaled

within the range of 0.0 to 100.0. Factory setting for the limit is 30.0.

In other words, there is leakage below this limit. A leak can be

expected if this value is exceeded.
To be able to make full use of the sensitivity of the detection process,

it is recommended to perform a ramp test with a calibrator after the

automatic initialization of the device. The ramp should cover the

standard operating range of the valve and correspond in steepness to

the approximate dynamic requirements of the application. During the

ramp test, parameter 15.ONLK of the diagnosics menu provides

information on the values shown by the leakage indicator. This allows

the limit for the leakage coefficient to be defined above the maximum

ramp test value.

Factor 1
Input of the factor for the threshold 1 error message. This factor refers

to the limit for the leakage indicator. Factory setting for factor 1 is 1.0.

That means, for C1.LIMIT = 30.0 and factor 1 = 1.0, the first leakage

error message is triggered at a leakage indication of 30.0.

Factor 2
Input of the factor for the threshold 2 error message. This factor refers

to the limit for the leakage indicator. Factory setting for factor 2 is 1.5.

That means, for C1.LIMIT = 30.0 and factor 2 = 1.5, the second

leakage error message is triggered at a leakage indication of 45.0.

Factor 3
Input of the factor for the threshold 3 error message. This factor refers

to the limit for the leakage indicator. Factory setting for factor 3 is 2.0.

That means, for C1.LIMIT = 30.0 and factor 3 = 2.0, the third leakage

error message is triggered at a leakage indication of 60.0.

C. LEAK

C1.LIMIT

C2.FACT1

C3.FACT2

C4.FACT3