Activation of the extended diagnostics
The extended diagnostics is deactivated at the factory, parameter 51 is

therefore at “OFF”. There are three operating modes for activating the

extended diagnostics:

S

On1: The extended diagnostics is activated and the threshold 3

error messages are also output via the fault message output.

S

On2: The extended diagnostics is activated, the threshold 2 error

messages are output via alarm output 2 and the threshold 3 error

messages are also output via fault message output.

S

On3: The extended diagnostics is activated, the threshold 1 error

messages are output via alarm output 1, the threshold 2 error

messages are output via alarm output 2 and the threshold 3 error

messages are also output via the fault message output.

.

NOTE
Please note that the menu items of the extended diagnostics from

A. PST to P. PAVG are only displayed in the display after selecting

one of the three On operating modes.
With the factory setting, the parameters of menu items A to P are

deactivated by default (OFF). The corresponding parameters are only

displayed once you have activated the relevant menu item with “On”.