beautypg.com

7 automatic initialization (structograms) – Siemens SIPART PS2 6DR52xx User Manual

Page 82

background image

Preparing for Operation

82

SIPART PS2 Manual

A5E00074631--06

.

NOTE
Make sure that the transmission ratio selector is in position 90 °!

5.

Switch on to the following display by pressing the operation mode
key

twice:

The following steps are identical with the steps 6) to 9) for initiali-

zation of linear actuators.
After successful initialization the determined part-turn range ap-

pears in the top display.
“5.INITM” appears in the bottom line again after pressing the op-
eration mode key

briefly. This brings you back to the Configu-

ration mode.

To exit the Configuration mode, press the operation mode key
for longer than 5 seconds. The software version is displayed after

about 5 seconds. The instrument is in manual operation after re-

leasing the operation mode key.

3.6.7

Automatic initialization (structograms)

Open

Closed

Up

Down

part-turn actuator

linear actuator

Figure 3-34

Direction of action of the actuators

The initialization procedure should be taken from the following structo-

gram (figure 3-35 to figure 3-38). The terms Open/Closed and up/down

in the structogram refer to the direction of action of the actuators as

illustrated in figure 3-34.

This manual is related to the following products: