Shifting the upper stop
This function is for detecting when the upper stop has changed its

value compared to the value during initialization by more than the

specified tolerance value. Monitoring is only possible if the valve is

within the tight closing function. The activation of the “top tight closing

function” (para“meter “39.YCLS”) is therefore prerequisite.

Threshold 1
First threshold for monitoring the upper limit stop. If the set absolute

value is exceeded during “top tight closing”, this will trigger the thres-

hold 1 error message.

Threshold 2
Second threshold for monitoring the upper limit stop. If the set absolute

value is exceeded during “top tight closing”, this will trigger the thres-

hold 2 error message.

Threshold 3
Third threshold for monitoring the upper limit stop. If the set absolute

value is exceeded during “top tight closing”, this will trigger the thres-

hold 3 error message.

.

NOTE
Monitoring of the lower and upper limit stops does not only react to

valve faults. A misadjustment of the position feedback is also detected

as a malfunction if the threshold values are exceeded.

G. OPEN

G1.LEVL1

G2.LEVL2

G3.LEVL3