Siemens SIPART PS2 6DR52xx User Manual
Page 77
Preparing for Operation
77
SIPART PS2 Manual
A5E00074631--06
5.
Switch on to the following display
by pressing the operation
mode key twice:
6.
Start initialization by pressing the increment key
for longer
than 5 s.
Display:
7.
After 5 s the display changes to:
(The display of the potentiometer setting is shown here and below
as an example only).
Now move the actuator to the position which you want to define as
the first of the two end positions with the increment
and decre-
ment
key. Then press the operation mode key
. This accepts
the current position as end position 1 and switches on to the next
position.
.
NOTE
If the message “RANGE” appears in the bottom line, the selected end
position is outside the permissible measuring range. There are several
ways to correct the error:
S
Adjust the friction clutch until “OK” appears and press the operation
mode key again or
S
move to another end position with the increment and decrement key
or
S
abort initialization by pressing the operation mode key. You then have
to change to P manual operation and correct the travel and the posi-
tion detection according to step 1.