Technical data 150 – Siemens SIPART PS2 6DR52xx User Manual
Page 150
Technical Data
150
SIPART PS2 Manual
A5E00074631--06
3-/4-wire device (terminals 2/4
and 6/8) (6DR52.. and 6DR53..)
• Power supply U
H
18 ... 35 V DC
18 ... 35 V DC
18 ... 30 V DC
18 ... 30 V DC
• Current consumption I
H
(U
H
- 7.5 V)/2.4 k
Ω [mA]
(U
H
- 7.5 V)/2.4 k
Ω [mA]
(U
H
- 7.5 V)/2.4 k
Ω [mA]
(U
H
- 7.5 V)/2.4 k
Ω [mA]
• Internal capacitance C
i
–
–
≤ 22 nF
–
• Internal inductance L
i
–
–
≤ 0.12 mH
–
• For connection to power circuits with –
–
intrinsically safe
U
o
≤ 30 V DC
I
k
≤ 100 mA
P
≤ 1 W
U
i
≤ 30 V DC
I
i
≤ 100 mA
Current input I
W
Rated signal range
0/4 ... 20 mA
0/4 ... 20 mA
0/4 ... 20 mA
0/4 ... 20 mA
Load voltage at 20 mA
≤ 0.2 V (corresponds to
10
Ω)
≤ 0.2 V (corresponds to
10
Ω)
≤ 1 V (corresponds to
50
Ω)
≤ 1 V (corresponds to
50
Ω)
Internal capacitance C
i
–
–
≤ 22 nF
–
Internal inductance (L
i
)
–
–
≤ 0.12 mH
–
For connection to power circuits with
–
–
intrinsically safe
U
o
≤ 30 V DC
I
k
≤ 100 mA
P
≤ 1 W
U
i
≤ 30 V DC
I
i
≤ 100 mA
Electrical isolation
between U
H
and I
W
between U
H
and I
W
between U
H
and I
W
(2 intrinsically safe cir-
cuits)
between U
H
and I
W
Test voltage
840 V DC (1 s)
840 V DC (1 s)
840 V DC (1 s)
840 V DC (1 s)
Connections
• Electric
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
EEx d certified cable
gland M20 x 1.5,
½-14 NPT or M25 x 1.5
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
Cable gland M20 x 1.5 or
½-14 NPT
• Pneumatic
Female thread G¼
DIN 45141 or ¼-18 NPT
Female thread G¼
DIN 45141 or ¼-18 NPT
Female thread G¼
DIN 45141 or ¼-18 NPT
Female thread G¼
DIN 45141 or ¼-18 NPT
External position sensor (potentiometer or NCS; as option)
• U
o
–
–
< 5 V
< 5 V
• I
o
–
–
< 75 mA
< 75 mA
• I
s
–
–
<160 mA
<160 mA
• P
o
–
–
<120 mW
<120 mW
Maximum permissible external capaci-
tance C
o
–
–
< 1
µF
< 1
µF
Maximum permissible external induc-
tance L
o
–
–
< 1 mH
< 1 mH
SIPART PS2
Basic device
without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
with EEx ia/ib protection
Basic device
with EEx n protection