beautypg.com

Siemens SIPART PS2 6DR52xx User Manual

Page 142

background image

Operation

142

SIPART PS2 Manual

A5E00074631--06

Messages on exiting configuration mode:

Upper lin

e

Lower lin

e

Aut

o

-

ma

tic

M

anua

lm

ode

P

m

anual

m

ode

Meaning/cause

Measure

4.nn.nn
VER

x

x

Software version

S

Wait

Error

SLnn

x

x

Monotony violation of the

free characteristic curve at

vertice n

S

Correct value

Messages during operation:

Upper lin

e

Lower lin

e

Aut

o

-

ma

tic

M

anua

lm

ode

P

m

anual

m

ode

Meaning/cause

Measure

CPU
START

x

x

Message after applying the

electrical power supply

S

Wait

HW /

ERROR

x

Hardware error

S

Replace electronics

NOINI

x

x

Positioner is not initialized

S

Start initialization

nnn.n

x

x

x

Actual position [in %] with

initialized positioner. Flashing

decimal point indicates com-

munication with a class 2

master

AUTnn

x

x

Automatic mode

(nn = setpoint)

MANnn

x

Manual mode (nn = setpoint)

S

Press operating mode
button to switch to
automatic mode

oFL / 127.9

x

x

x

Display range was exceeded.

Possible causes:
S

friction clutch or

S

transmission ratio selector
were misadjusted or

S

positioner was fitted on
another actuator without
re-initialization.

S

Adjust friction clutch in
such a way that the
indication of the actual
value remains between
0.0 and 100.0 on

moving the actuator or

S

switch over the
transmission ratio
selector or

S

set to the factory setting
(preset) and initialize

EXSTP

x

x

Actuator was stopped via

binary input

EX UP

x

x

Actuator is moved to the

upper stop via binary input

EXDWN

x

x

Actuator is moved to the

lower stop via binary input

EXTPSt

Partial stroke test was

activated e.g. via binary input

InPSt

cyclic partial stroke test

HTCNF

x

x

x

x

HARD configuration running

This manual is related to the following products: