Operation
142
SIPART PS2 Manual
A5E00074631--06
Messages on exiting configuration mode:
Upper lin
e
Lower lin
e
Aut
o
-
ma
tic
M
anua
lm
ode
P
m
anual
m
ode
Meaning/cause
Measure
4.nn.nn
VER
x
x
Software version
S
Wait
Error
SLnn
x
x
Monotony violation of the
free characteristic curve at
vertice n
S
Correct value
Messages during operation:
Upper lin
e
Lower lin
e
Aut
o
-
ma
tic
M
anua
lm
ode
P
m
anual
m
ode
Meaning/cause
Measure
CPU
START
x
x
Message after applying the
electrical power supply
S
Wait
HW /
ERROR
x
Hardware error
S
Replace electronics
NOINI
x
x
Positioner is not initialized
S
Start initialization
nnn.n
x
x
x
Actual position [in %] with
initialized positioner. Flashing
decimal point indicates com-
munication with a class 2
master
AUTnn
x
x
Automatic mode
(nn = setpoint)
MANnn
x
Manual mode (nn = setpoint)
S
Press operating mode
button to switch to
automatic mode
oFL / 127.9
x
x
x
Display range was exceeded.
Possible causes:
S
friction clutch or
S
transmission ratio selector
were misadjusted or
S
positioner was fitted on
another actuator without
re-initialization.
S
Adjust friction clutch in
such a way that the
indication of the actual
value remains between
0.0 and 100.0 on
moving the actuator or
S
switch over the
transmission ratio
selector or
S
set to the factory setting
(preset) and initialize
EXSTP
x
x
Actuator was stopped via
binary input
EX UP
x
x
Actuator is moved to the
upper stop via binary input
EXDWN
x
x
Actuator is moved to the
lower stop via binary input
EXTPSt
Partial stroke test was
activated e.g. via binary input
InPSt
cyclic partial stroke test
HTCNF
x
x
x
x
HARD configuration running