beautypg.com

5 pneumatic connection – Siemens SIPART PS2 6DR52xx User Manual

Page 71

background image

Preparing for Operation

71

SIPART PS2 Manual

A5E00074631--06

3.5 Pneumatic Connection

!

WARNING
For reasons of safety, the pneumatic power may only be supplied after

assembly when the positioner is switched to operating level P manual

operation with electrical signal applied (as-delivered state, see

figure 4-4, page 92).

.

NOTE
Note the air quality! Oil-free industrial air, solid content < 30 μm, pressure

dew point 20 K below the lowest ambient temperature (chapter 7 “Techni-

cal Data”, page 153).

S

Connect a manometer block for supply air and actuating pressure if

necessary.

S

Connection by female thread G 1/4 DIN 45141 or 1/4” NPT:
P

Z

Supply air 1.4 to 7 bar

Y1

Actuating pressure 1 for single- and double-acting actuators

Y2

Actuating pressure 2 for double-acting actuators

E

Exhaust air outlet (remove silencer if necessary)

see figure 2-4 and 2-5, page 19.

S

Safety position when the electric power supply fails:
single-acting:

Y1

deaerated

double-acting:

Y1

Max. Actuating pressure

(supply air pressure)

Y2

deaerated

S

Connect actuating pressure Y1 or Y2 (only in double-acting actua-

tors) according to the desired safety position.

S

Connect supply air to P

Z

.

.

NOTE
In order for spring-loaded pneumatic actuators to be able to reliably

exploit the maximum possible travel, the supply pressure must be

sufficiently greater than the maximum required final pressure of the

actuator.
After installing the device, check the pneumatic connections of the entire

assembly for leakage. Any leakage would cause not only continuous

consumption of compressed air but also would cause the positioner to

continually endeavor to compensate for the variance in position, leading

in time to premature wear of the whole control mechanism.