Preparing for Operation

79

SIPART PS2 Manual

A5E00074631--06

3.6.4

Preparations for part-turn actuator

.

NOTE
Very important:
Switch the transmission ratio selector in the

positioner (8, figure 2-2, page 17) to position 90° (normal angle for

part-turn actuator).

1. Mount the positioner with the appropriate mounting kit

(see chapter 3.3.5, page 52).

2. Connect the actuator and the positioner with the pneumatic lines

and supply pneumatic power to the positioner (figure 2-4 and 2-5,

page 19).

3. Connect a suitable current or voltage source (see figure 3-13,

page 59 and figure 3-20, page 63).

4. The positioner is now in the operating mode “P-manual

operation” The current potentiometer voltage (P) is displayed in %

in the top line of the display, e.g.: “P12.3“, and “NOINI” flashes in

the bottom line:

5. Check the free running of the mechanics in the whole actuating

range by moving the actuator with the keys

and

and driving

to the respective end position.

.

NOTE
You can move the actuator quickly by pressing the other direction key

additionally whilst keeping the direction key selected first pressed.

3.6.5

Automatic initialization of part-turn actuator

If you can move the actuator correctly through the actuating range,

leave it standing in a central position and start automatic initialization:

1. Press the operation mode key

for longer than 5 s. This brings

you to the configuration operating mode.