beautypg.com

Siemens SIPART PS2 6DR52xx User Manual

Page 108

background image

Operation

108

SIPART PS2 Manual

A5E00074631--06

Monitoring time for setting the fault messages
The set value(s) is/are for the specification of the time, within which the

positioner must have reached a compensated state. The corresponding

response threshold is preset with “49. LIM”.
If the set time is exceeded, the fault message output is set.

.

NOTE
If the tight closing function is activated, for parameter “49. LIM”, the

monitoring of the control deviation in each overrun direction (YCDO:

< 0 %, YCUP: > 100 %) is deactivated. This function is particularly

useful for valves with a soft seat. For the long-term monitoring of the

endstop positions, we recommend activating the parameters

“F. ZERO” and “G. OPEN”.
You can find more information on fault messages in chapter 4.5.3

Online Diagnostics.

Response threshold for fault messages
A value (%) can be set here for the permissible control deviation for

triggering the fault message.
If parameters 48 and 49 are set to “Auto” (factory setting), the fault

message is set if the short step zone is not reached within a certain

time. Within 5 to 95 % of the actuator travel, this time is 10 to 90 % of

10 times the initialization actuating time.

Preset
Establishes the factory setting and resets the initialization.

.

NOTE
After “Preset” the positioner needs to be re-initialized. All previously

determined maintenance parameters are deleted.

48. TIM

49. LIM

50.PRST

This manual is related to the following products: