Operation
141
SIPART PS2 Manual
A5E00074631--06
Measure
Meaning/cause
Lower lin
e
Upper lin
e
UP >
x
“UP” tolerance range exceeded or
inactive zone of the potentiometer
passed
S
Increase effective lever length for
linear actuators or switch
transmission ratio selector to
90 degrees
S
Press operating mode button briefly
to acknowledge
S
Restart initialization
90_95
x
Only possible for part-turn actuators:
Actuator travel is not within the range
of 90 to 95%
S
Use the “+” and “--” buttons to move it
to the range between 90 and 95%
S
Press operating mode button briefly
to acknowledge
U--d>
x
“Up-Down” measuring span fallen
short of
S
Reduce effective lever length for
linear actuators or switch
transmission ratio selector to
33 degrees
S
Press operating mode button briefly
to acknowledge
S
Restart initialization
U nn.n
D-->U
x
x
Display of actuating time “Up”
S
Wait, or
S
press the “--” button to interrupt the
initialization process to change the
actuating time, or
S
activate the leakage test with the “+”
button
d nn.n
U-->d
x
x
Display of the actuating time “Down”
S
Wait, or
S
press the “--” button to interrupt the
initialization process to change the
actuating time, or
S
activate the leakage test with the “+”
button
NOZZL
x
Actuator stationary (initialization was
interrupted with the “--” button during
the indication of the actuating speed)
S
Actuating time can be changed by
adjusting the reactor(s)
S
press the “--” button to repeat the
determination of the actuating speed
S
continue with the “+” button
TESt
LEAKG
x
x
Leakage test active (“+“ button was
pressed during the indication of the
actuating speed)
S
Wait one minute
S
continue with the “+” button
nn.n
_
oMIN
x
x
Value and unit of the result after the
leakage test
S
Eliminate if leakage value is too great
S
continue with the “+” button
nn.n
FINSH
x
x
Initialization was completed
successfully, possibly along with the
indication of the actuator travel or
angle
S
Press the operating mode button
briefly to acknowledge and exit the
configuration level by pressing it
continuously