beautypg.com

Siemens SIPART PS2 6DR52xx User Manual

Page 141

background image

Operation

141

SIPART PS2 Manual

A5E00074631--06

Measure

Meaning/cause

Lower lin

e

Upper lin

e

UP >

x

“UP” tolerance range exceeded or

inactive zone of the potentiometer

passed

S

Increase effective lever length for

linear actuators or switch

transmission ratio selector to

90 degrees

S

Press operating mode button briefly

to acknowledge

S

Restart initialization

90_95

x

Only possible for part-turn actuators:

Actuator travel is not within the range

of 90 to 95%

S

Use the “+” and “--” buttons to move it

to the range between 90 and 95%

S

Press operating mode button briefly

to acknowledge

U--d>

x

“Up-Down” measuring span fallen

short of

S

Reduce effective lever length for

linear actuators or switch

transmission ratio selector to

33 degrees

S

Press operating mode button briefly

to acknowledge

S

Restart initialization

U nn.n
D-->U

x

x

Display of actuating time “Up”

S

Wait, or

S

press the “--” button to interrupt the

initialization process to change the

actuating time, or

S

activate the leakage test with the “+”

button

d nn.n
U-->d

x

x

Display of the actuating time “Down”

S

Wait, or

S

press the “--” button to interrupt the

initialization process to change the

actuating time, or

S

activate the leakage test with the “+”

button

NOZZL

x

Actuator stationary (initialization was

interrupted with the “--” button during

the indication of the actuating speed)

S

Actuating time can be changed by

adjusting the reactor(s)

S

press the “--” button to repeat the

determination of the actuating speed

S

continue with the “+” button

TESt
LEAKG

x

x

Leakage test active (“+“ button was

pressed during the indication of the

actuating speed)

S

Wait one minute

S

continue with the “+” button

nn.n

_

oMIN

x

x

Value and unit of the result after the

leakage test

S

Eliminate if leakage value is too great

S

continue with the “+” button

nn.n
FINSH

x

x

Initialization was completed

successfully, possibly along with the

indication of the actuator travel or

angle

S

Press the operating mode button

briefly to acknowledge and exit the

configuration level by pressing it

continuously

This manual is related to the following products: