Fault indication

(symptoms)

possible cause(s)

Remedies

SIPART PS2 stops during

“RUN 1”.

Initialization started from end

position and

reaction time of max. 1 min.

not waited for.

Mains pressure not connected

or insufficient.

Up to 1 min. delay time

required.

Do not start initialization from

end position.

Secure the mains pressure.

SIPART PS2 stops during

“RUN 2”.

Transmission ratio selector and

parameter 2 (YAGL) as well as

actual stroke do not match.

Stroke not correctly set for

lever.

Piezo valve(s) do(es) not

switch (see table 6).

Check settings:

see leaflet: figure “device view

(7)” as well as parameters 2

and 3

Check stroke setting at lever.

see table 2

SIPART PS2 stops during

“RUN 3”.

Actuating time too high.

Open reactor completely

and/or set PZ pressure (1) to

maximum permissible value.

If necessary, use booster.

SIPART PS2 stops during

“RUN 5”and does not reach

“FINISH” (delay time:

> 5 min).

“Batches” (play) in the

positioner -- actuator -- control

valve system

Part-turn actuator:

Check if set screw of the

coupling wheel is inserted

firmly

Linear actuator:

Check if lever is connected

firmly to positioning shaft.

Eliminate any other play

between actuator and control

valve.

Table 5

Fault indication

(symptoms)

possible cause(s)

Remedies

For SIPART PS2, “CPU

test” flashes in the display

(approx. every 2 sec).

Piezo valve(s) do(es) not

switch.

Water in the pneumatic block

(due to wet compressed air)

At an early stage, this fault can

be eliminated by subsequent

operation with dry air (if ne-

cessary, in the temperature

cabinet at 50 to 70°C).

In manual or automatic

mode, the actuator cannot

be moved or only in one

direction.

Moisture in the pneumatic

block

Otherwise: Repair

(see chapter 5, page 145)

Piezo valve(s) do(es) not

switch (no quiet “clicking”

can be heard when the + or

– button is pressed in

Screw between shrouding

cover and pneumatic block not

tightened firmly or cover

jammed.

Tighten screw, if necessary

eliminate jam.

button is pressed in

manual mode).

Dirt (chips, particles) in the

pneumatic block

Repair (see chapter 5,

page 145) or new device;

integrated fine screen,

also replace and clean.

Deposits on contact(s)

between electronics board and

pneumatic block can develop

due to abrasion as a result of

continuous high vibration

stress.

Clean all contact surfaces with

spirit; if necessary, re-bend the

pneumatic block springs

slightly.

Table 6