Technical data 151 – Siemens SIPART PS2 6DR52xx User Manual

Page 151

background image

Technical Data

151

SIPART PS2 Manual

A5E00074631--06

Technical specifications

Option modules

Without Ex protection
(EEx d also)

With Ex protection EEx ia/ib

With Ex protection EEx n

Ex protection to EN 50014, EN 50020 and
EN 50021

II 2G EEx ia/ib II C T4/T5/T6

II 3G EEx nA L [L] II C T6

Mounting location

Zone 1

Zone 2

Permissible ambient temperature for opera-
tion
(For devices with Ex protection: Only in con-
junction with the basic device 6DR5... -.E....
Only T4 is permissible when using I

y

module)

-30 ... +80 °C (-22 ... +176 °F)

T4: -30 ... +80 °C (-22 ... +176 °F)

1)

T5: -30 ... +65 °C (-22 ... +149 °F)

1)

T6: -30 ... +50 °C (-22 ... +122 °F)

1)

Alarm module

6DR4004-8A (without Ex protec-
tion)

6DR4004-6A (with Ex protection) 6DR4004-6A (with Ex protection)

Binary alarm outputs A1, A2 and alarm output

Signal status High (not responded)
Signal status Low* (responded)
(* Low is also the status when the basic
device is faulty or has not electric power sup-
ply)

Active, R = 1 k

Ω, +3/-1%*

Disabled, I

R

< 60 µA

≥ 2.1 mA

≤ 1.2 mA

≥ 2.1 mA

≤ 1.2 mA

(* When used in the flameproof
casing the current consumption
is limited to 10 mA per output.)

(Switching threshold with sup-
ply to EN 60947-5-6: U

H

= 8.2 V,

R

i

= 1k

Ω)

(Switching threshold with sup-
ply to EN 60947-5-6: U

H

= 8.2 V,

R

i

= 1k

Ω)

Internal capacitance C

i

≤ 5.2 nF

Internal inductance L

i

Negligible

Power supply U

H

≤ 35 V

Connection to power circuits with

intrinsically safe switching
amplifier EN 60947-5-6
U

o

≤ 15.5 V DC

I

k

≤ 25 mA, P ≤ 64 mW

U

i

≤ 15.5 V DC

Binary input BE2

• Electrically connected to the basic device

- Signal status 0

Floating contact, open

Floating contact, open

Floating contact, open

- Signal status 1

Floating contact, closed

Floating contact, closed

Floating contact, closed

- Contact load

3 V, 5

µA

3 V, 5

µA

3 V, 5

µA

• Electrically isolated from the basic device

- Signal status 0

≤ 4.5 V or open

≤ 4.5 V or open

≤ 4.5 V or open

- Signal status 1

≥ 13 V

≥ 13 V

≥ 13 V

- Natural resistance

≥ 25 kΩ

≥ 25 kΩ

≥ 25 kΩ

Static destruction limit

± 35 V

Internal inductance and capacitance

Negligible

Connection to power circuits

Intrinsically safe U

i

≤ 25.2 V

U

i

≤ 25.2 V DC

Electrical isolation

The 3 outputs, the input BE2 and the basic device are electrically isolated from each other

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

SIA module (not for EEx d version)

6DR4004-8G (without Ex protec-
tion)

6DR4004-6G (with Ex protec-
tion)

6DR4004-6G (with Ex protec-
tion)

Limit transmitter with slot-type initiators and
alarm output

2-wire connection

Ex protection

Without

II 2 G EEx ia/ib IIC T6

II 3 G EEx nA L [L] IIC T6

Connection

2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side

2 slot-type initiators

Type SJ2-SN

Type SJ2-SN

Type SJ2-SN

Function

NC (normally closed)

NC (normally closed)

NC (normally closed)

Connection to power circuits with

nominal voltage 8 V
Current consumption:

≥ 3 mA (limit value not
responded)

≤ 1 mA (limit value
responded)

Intrinsically safe switching
amplifier EN 60947-5-6
U

i

≤ 15.5 V DC

I

i

≤ 25 mA, P

i

≤ 64 mW

U

i

≤ 15.5 V DC

P

i

≤ 64 mW

Internal capacitance

≤ 41 nF

Internal inductance

≤ 100 mH

Electrical isolation

The 3 outputs are electrically isolated from the basic device

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

Alarm output

See Alarm module

See Alarm module

See Alarm module

1)

Only in conjunction with the basic device 6DR5...-E..... With Iy module only T4 permitted.