Selecting a Location
The location you select for installing the system hardware must
meet the following requirements:
■
19-inch EIA-standard grounded rack or table capable of
supporting at least 154 kg (340 lb). A fully-loaded switch
weighs 77 kg (170 lbs).
■
At least 2 inches (5.2 cm) on either side of the chassis, and
from the front and rear of the chassis, to allow adequate
airflow through the chassis (Figure1).
Figure 1. Air Flow Requirements
■
AC power source(s) within 2 m (9 ft) (separate sources, on
separate circuits, if you require maximum fault tolerance)
■
Ambient temperature between 0°C and 40°C (32°F to 104°F)
■
Relative humidity less than 95%, non-condensing