GT10/GT30
4.12 Connecting with a PLC by Omron Corp.
70
Communicating with a peripheral board
The system areas should be set as indicated below.
Address
Value set
Setting contents
DM6600
0201 (HEX)
PLC main unit mode setting (monitor mode)
DM6550
0001 (HEX)
RS232C port mode setting (higher–order link)
DM6551
0004 (HEX)
Communication conditions settings (19200 bits/s, 7 bits, even, 1 bit)
Devices that can be used
Device type
Address range
Points
Relay area
0000CH to 0252CH
253 words
Data memory area
DM0000 to DM6143
6143 words
NOTES
Depending on the type being used, the address range may be
limited to a small range. Please refer to the instruction manual of
the PLC being used for detailed information.
Data cannot be written to relay areas 253–255CH.