3 error codes and how to handle them, 1 gt series error codes, Gt series error codes – Motorola GT10 User Manual
Page 165
GT10/GT30
9.3 Error Codes and How to Handle Them
142
9.3
Error Codes and How to Handle Them
When an error occurs in the GT series, an error code displays at the top right of the
screen. There are two types of error codes:
GT series error codes
PLC error codes
ER XX
Error code display
9.3.1
GT Series Error Codes
When connected to a FP series PLC
The following three types of error codes are displayed when there is an error in the GT
main unit:
Code no.
Content
Cause and solution
FF
Time up error
No response from the PLC.
1) The PLC connection cable is disconnected. Check the connection
cable to make sure it is connected.
2) There is a temporary error due to noise, etc. Re–supply power to the
PLC and GT main unit.
21
Data error
A data error occurred dur-
ing communication.
1) An error exists in the communication condition settings. Check the
PLC and GT main unit communication speed and transfer format.
2) There is a temporary error due to noise, etc. Re–supply power to the
PLC and GT main unit.
22
Overrun error
The GT main unit cannot
receive data.
The reception buffer in the GT main unit is overflowing.
There could be an error in the PLC.
Re–supply power to the PLC and GT main unit.
When connected to a PLC (FX) series made by Mitsubishi Electric
The following four types of error codes are displayed when there is an error in the GT
main unit:
Code no.
Content
Cause and solution
FF
Time up error
No response from the PLC.
Check the connection cable to make sure it is connected.
10
Data error
A data error occurred dur-
ing communication.
Check to see if there is an error in the communication parameters
settings.
12
Overrun error
The GT main unit cannot
receive data.
The problem may be caused by a runaway PLC.
61
PLC error
A NAK error has been re-
turned by the PLC.