4.9 Automatic Communication Settings Function

58

4.9

Automatic Communication Settings Function

After turning on the power supply, if there is no response from the PLC connected to

the GT10/GT30, the GT10/GT30 switches to the automatic setting mode for the

communication conditions. In the automatic setting mode, commands are sent to the

PLC while changing the communication conditions in the sequence shown below.

GT10

PLC

(1) 9600 bits/s, 8 bits, odd parity, 1 stop bit

(2) 19200 bits/s, 8 bits, odd parity, 1 stop bit

(3) 115200 bits/s, 8 bits, odd parity, 1 stop bit

(4) Communication conditions set in GTWIN Configuration Settings

If there is no response from the PLC,

commands are sent to the PLC while

changing the communication conditions.

The GT10/GT30, in automatic setting mode, continues to repeat steps (1) to (4) until

there is a response from the PLC. While it is repeating these steps, it is in the “Standby”

mode under “GT10/GT30 Configuration” a “Communication Parameters” a “Handle

Communication Error” on GTWIN. For information on how settings are entered, please

refer to page 75 (GT10) and page 97 (GT30).

EXPLANATION

Conditions when the automatic settings mode is in effect

If communication is attempted the specified number of times and

there is no response from the PLC, the GT10/GT30 goes into the

automatic settings mode. The number of attempts is specified using

the “No. of Retries” parameter under “GT10/GT30 Configuration”

“Communication Parameters” “Handle Communication Error” on

GTWIN. For information on how settings are entered, please refer to

page 75 (GT10) and page 97 (GT30).
Automatically set communication conditions

In the automatic settings mode, if there is a response from the PLC,

subsequent communication is carried out under conditions

matching the response. The main unit configuration settings are not

updated, however, even if the communication parameters are

different from those of the main unit configuration settings.

CAUTION

An error response from the PLC is taken as a response, and the

GT10/GT30 does not go into the automatic settings mode.
If the unit is connected to the COM port of the

FP0/FP1/FP2/FP2SH/FP–M, communication between the FP device