beautypg.com

Using the sysmac cs1 series (1 : 1) – Motorola GT10 User Manual

Page 91

background image

GT10/GT30

4.12 Connecting with a PLC by Omron Corp.

68

Using the SYSMAC CS1 series (1 : 1)

CPU

Link I/F

Wiring diagram

GT series

CS1H–CPU67

CS1H–CPU66

CS1H–CPU65

CS1H–CPU64

CS1H–CPU63

CS1G–CPU45

CS1G–CPU44

CS1G–CPU43

CS1G–CPU42

RS232C port on

CPU unit

D–sub 9–pin on Omron PLC side

SD

SD

RD

RD

RS

RS

CS

CS

GND

GND

GT main unit side

Pin no.

Abbreviation

1

FG

2

SD

3

RD

4

RS

5

CS

Pin no. Abbreviation

6
7
8
9

SG

GT10/GT30

Peripheral port on

CPU unit *

1

1

FG

2

RD

3

SD

4

CS

5

RS

Pin no. Abbreviation

SD

SD

RD

RD

RS

RS

CS

CS

GND

GND

GT main unit side

Pin no. Abbreviation

6
7

SG

.
.
25

Connection cable for the

peripheral port (25–pin)

CS1W–SCU21

D–sub 9–pin on Omron PLC side

SD

SD

RD

RD

GT main unit side

Pin no.

Abbreviation

1

FG

2

SD

Pin no. Abbreviation

CS1W–SCB21

RD

RD

RS

RS

CS

CS

GND

GND

2

SD

3

RD

4

RS

5

CS

6

CS1W–SCB41

6
7
8
9

SG

*1 The CS1W–CN225 or CS1W–CN625 cable is required in order to connect a

peripheral board.

REFERENCE

For the contents of error codes, please refer to “Error Codes and How

to Handle Them” on page 142.

Setting the communication conditions
Setting the communication conditions for the GT main unit
The following settings should be entered for the COM port communication condition

settings.

Item

Value Set

Communication speed setting

19200 bits/s

Data length

7 bits

Parity check

Yes, Even

Stop bits

1 bit