2) arithmetic instructions – Hitachi NJI-350B User Manual
Page 95

Chapter 5 Instruction Specifications
5-45
Item number
Arithmetic instructions-1
Name
Substitution statement (ASSIGNMENT STATEMENT)
Ladder format
Condition code
Processing time (
µs)
Remark
R7F4
R7F3
R7F2
R7F1
R7F0
Average Maximum
d = s
DER
ERR
SD
V
C
↕
z
z
z
z
Instruction format
Number of steps
(See following table)
Condition
Steps
d = s
(See Notes)
Bit
Word
Double word
Usable I/O
X
Y
R,
M
TD, SS,
CU, CT
WX WY
WR,
WM TC DX DY
DR,
DM
C
onstant
Other
d
Substitution destination
{
{
{
{
{
{
{
s
Substitution source
{
{
{
{
{
{
{
{
{
{
{
( ) Index value
{
{
{
Function
• Substitutes the content of s into d.
• It is possible to use array variables for d and s.
• When d is a word, the constant is
0 to 65535 or – 32768 to + 32767 (decimal)
H0000 to HFFFF or H8000 to H7FFF (hexadecimal)
When d is a double word, the constant is
0 to 4294967295 or -2147483648 to +2147483647 (decimal)
H00000000 to HFFFFFFFF or H80000000 to H7FFFFFFF
Notes
• When using an array variable, DER is set to 1 if the usable I/O number exceeds the maximum value, and DER is reset to “0”
if it is normal.
• The combinations of d and s are as follows:
d
s
Bit
Bit
Word
Word
Double word
Double word
• Step numbers and processing time are as follows:
Processing time (
µs)
d
s
Number of steps ( ) indicates DW
Bit
Word
Double word
I/O
I/O
3 (4)
32
27
35
I/O
Array
4
74
66
86
Array
I/O
4 (5)
52
53
71
Array
Array
5
92
99
120
d =