Chapter 13 Troubleshooting

13-8

(b)

Will not operate (will not run)
Even if the PLC operation conditions are met, the CPU does not operate (the RUN LED does not turn on) and
remains stopped. However, the peripheral units go on-line.

Caution

If the CPU is WRITE-occupied, the CPU will not run even if the RUN switch is switched from “STOP” to “RUN.” The
CPU starts running by pressing the GRS key after peripheral units are connected.

Check the memory

Perform CPU initialization
Set memory parameters
Reset the power
Replace CPU if above steps
does not remedy the problem

NO

YES

YES

NO

Serious user program error

45

44

34

23

Self-diagnostic error code

Serious memory error

33

31

Self-diagnostic error code

Check the user program

• Check programs using

peripheral devices

• Error special internal output

monitor

• Verify scan time
• Correct program

Check I/O assignments

• Check the assignment table at

peripheral devices

• Can I/O assignment be

corrected?

• Malfunction due to noise

27