Chapter 13 Troubleshooting

13-11

Data cannot be entered.

I/O assignment error is generated, but data is read.

NO

YES

YES

NO

YES

NO

NO

YES

Is there a wiring

error, disconnection

or loose screw on the

terminal block?

Replace the terminal block

Contact our service department

Contact our service department

Perform rewiring

Check the wiring systems
Change the voltage to satisfy
the specifications

Is there input

when the voltage is

checked between

the common and bit

on the input side?

Is the LED lit?

Is there an error on the

internal contactors on the

terminal stand?

YES

NO

YES

NO

Are the program and I/O

assignment correct?

Replace the expansion cable

Correct the error

Replace the expansion unit

Is the cable in the

expansion unit

damaged?