Chapter 12 Error Code List and Special Internal Outputs

12-7

No.

Name

Meaning

Description

Setting

condition

Resetting

condition

R7EB Clear retentive area

1: Clear retentive area

R7EC Clear error code

1: Clear error code in WRF000 to F00A, R7C8 to 7DE

Set by user

Cleared by
the system

R7ED Undefined

Do not use.

R7EE Battery error

detection
enable/disable

1: Detection enabled
0: Detection disabled

Be sure to set if battery is used.

Set by user

Cleared by
user, or when
retentive area
is cleared, or
the CPU is
initialized.

R7EF Backup memory

writing execution
flag

1: Being written

R7F0 Carry flag (CY)

0: No carry
1: Carry

Indicates whether there is a carryover
from the operation result

R7F1 Overflow flag (V)

0: No overflow
1: Overflow

Indicates whether there is overflow in
the operation result

Set by the
system *3

Cleared by
the system

R7F2 Shift data (SD)

0: Shift data “0”
1: Shift data “1”

Designates the shift data used in shift
instructions, etc.

Set by user

Cleared by
user

R7F3 Operation error

(ERR)

0: Normal
1: Error

Indicates whether there is an operation
error when operation is executed

R7F4 Data error (DER)

0: Normal
1: Error

Indicates whether there is a data error
when operation is being executed.

Set by the
system

R7F5 Special I/O function

setting flag

1: Request to set

For counter, PWM and pulse train

R7F6 Special I/O

parameters to write in
FLASH *4

1: Request to write

For counter, PWM and pulse train

Set by user

R7F7 Special I/O parameter

error

0: Normal
1: Error

Indicates the results of the special I/O
parameter settings.

Set by the
system

R7F8 Calendar, clock read

request

1: Request to read

Read the present values of calendar,
clock and set in WRF01B to WRF01F

R7F9 Calendar, clock

setting request

1: Request to write

Set the data set in WRF01B to
WRF01F in the calendar and clock

R7FA Clock

± 30 second

adjustment request

1: Request adjustment

When second data (WRF00F) is 0 to
29, it becomes 0 seconds and when it is
30 to 59, +1 minute is added and
second data becomes 0

Set by user

R7FB Calendar and clock

set data error

0: Normal
1: Error

Indicates whether there is an error in
calendar and clock set data

Set by the
system

Cleared by
the system

R7FC Output control 1
R7FD Output control 2
R7FE Output control 3

R7FF Output control 4

0: Output disabled
1: Output enabled

Sets the enabling and disabling when
Y100 through Y103 is used as PWM
output, pulse output, and counter
coincidence output.

Set by user

Cleared by
user
(Cleared by
the system in
case of pulse
output)

*3:

Cleared by system even when Set by user.

*4:

The word special internal output that can be written using this function is shown in Table 12.1 on the following page.