Chapter 9 PLC Operation

9-7

(3)

Continuation of operation after a congestion error occurred

If an interrupt scan congestion error occurs when the special internal output bit R7C2, which specifies whether the
operation should continue after a congestion error, is turned on, the interrupt scan is started anew and the scan is
executed from the beginning again. Therefore, if the operation continuation specification of the normal scan is Off under
the conditions where interrupt inputs are frequently entered from the external source, this scan is stopped as a normal
scan congestion error. If the operation continuation specification of the normal scan is On, only interrupt scans are
continuously executed depending on the condition of the interrupt congestion error. Care must be taken because normal
scans are not executed under this condition.

Figure 9.14 Operation when operation continuation at congestion error is set

INT16

INT16

INT16

Normal
scan

END scan processing
Program execution

Periodical system processing

Interrupt analysis
processing
Interrupt scan

Congestion check time

Interrupt contact on

Interrupt
scan

Interrupt contact on

Interrupt contact on

R7C0 On/R7C2 On: Continue

R7C0 Off/R7C2 On: Stop