beautypg.com

Hitachi NJI-350B User Manual

Page 71

background image

Chapter 5 Instruction Specifications

5-21

Item number

Basic instructions-11, 12

Name

Set/reset coil output (SET, RES)

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

DER

ERR

SD

V

C

Upper case: SET

n

SET

n

RES

S

R

n

SET

n

RES

z

z

z

z

z

0.9

Lower case: RES

Instruction format

Number of steps

SET n

Condition

Steps

RES n

1

0.9

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

n

I/O number

{

{

Function

n

SET

SET n

Switches on the device when the operation result obtained up to that point is “1.”

The device that is switched on will not be switched off even if the operation result is “0.”

n

RES

RES n

Switches off the device when the operation result obtained up to that point is “1.”

( ) indicates the display when the Ladder Editor is used.

Notes

• When a set/reset coil is used on a multi-layer coil, it must be set to the highest level or an arbitrary contact must be entered

immediately before the use.

Example of OK

Example of NG

SET

SET

SET

SET

SET

Program example

X00000

X00001

R100

R100

LD
SET
LD
RES

X00000
R100
X00001
R100

SET

RES

Program description

• When input X00000 turns on, output R100 turns on. Even if X00000 turns off, R100 remains on.
• When input X00001 turns on, output R100 turns off.
• When input X00000 and X00001 both turn on, the one executed later than the other during programming takes a higher

priority.

S

E

T

n

R

ES

n