Chapter 5 Instruction Specifications

5-28

Item number

Basic instructions-22

Name

On delay timer (ON DELAY TIMER)

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

DER

ERR

SD

V

C

z

z

z

z

z

Instruction format

Number of steps

1.4

Condition

Steps

OUT TD n t s

5

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

n

Timer number

{ 0 to 255 (Decimal)

t

Time base

.01s, .1s, 1s

s

Set value

{

{

{

{ 1 to 65535 (Decimal)

Function

• The progress value is updated when the startup condition is on, and the coil turns on when the progress value is greater than

or equal to the set value.

• If the startup condition is turned off, the progress value is cleared and the coil turns off.
• The progress value is set in TC n and does not exceed 65535 (decimal).
• If the progress value is updated during RUN, the operation will be performed using the new progress value at that point.
• If an I/O is set for the set value, the set value can be changed during operation by changing the I/O value, since the set values

are updated during each scan.

Notes

• The .01s time base can only be used for timer numbers 0 to 63 (64 points).
• The .1 s and 1 s time bases can be used for all timer numbers (0 to 255).
• A maximum of 256 points can be used for the timers TD, SS, CU, CTU and CTD in total.

However, the same area as the counter is used. The timer numbers and counter numbers may not be overlapped.

Program example

X00000

TD10

LD

X00000

OUT

TD10 0.01S 12345

LD

TD10

OUT

R100

TD10

R100

0.01S 12345

• An example of a word I/O being used as the set value for the circuit shown above.

R7E3

X00000

TD10

0.01S WR0010

TD10

R100

WR0010=12345

LD

R7E3

[
WR0010=12345
]
LD

X00000

OUT

TD10 0.01S WR0010

LD

TD10

OUT

R100

TD n

t x s

OU
T
TD
n

t

s