6) fun instructions – Hitachi NJI-350B User Manual
Page 174

Chapter 5 Instruction Specifications
5-124
Item number
FUN instructions-1
Name
General purpose port switching
Ladder format
Condition code
Processing time (
µs)
Remark
R7F4
R7F3
R7F2
R7F1
R7F0
Average Maximum
FUN 5 (s)
DER
ERR
SD
V
C
↕
z
z
z
z
Instruction format
Number of steps
114
-
Condition
Steps
FUN 5 (s)
—
3
Bit
Word
Double word
Usable I/O
X
Y
R,
M
TD, SS,
CU, CT
WX WY
WR,
WM TC DX DY
DR,
DM
C
o
nstant
Other
s
Argument
{
s+1
(system area)
{
s+2
(system area)
{
Function
This command is to switch dedicated port (programming port) to general purpose port.
S
Port number
Current setting
System area
System area
S+1
S+2
Port number
H01 : Port 1
H02 : Port 2
* Error with the other values
Current setting
H00 : Dedicated port (Programming port)
H01 : Port 1 is general purpose port
H02 : Port 2 is general purpose port
Notes
• General purpose port can be configured only one port. If either port is configured general purpose port, FUN 5 command for
the other port is ignored with DER=1.
• General purpose works only when CPU is in RUN mode. When CPU status is in STOP, the port is automatically switched
back to dedicated port (programming port).
• It is impossible to switch from general purpose to dedicated port while CPU is in RUN status.
• FUN 5 does not work if port 1 is configured as modem mode.
Program example
X00000
DIF0
LD X00000
AND DIF0
[
WR0100 = H0200
]
WR0100 = H0200
FUN 5 (WR0100)
FUN 5 (WR0100)
Program description
Port 2 is switched to general purpose port at rising edge of X0000 input.
F