Chapter 5 Instruction Specifications
5-126
Item number
FUN instructions-3
Name
I/O refresh (Input/output)
Ladder format
Condition code
Processing time (
µs)
Remark
R7F4
R7F3
R7F2
R7F1
R7F0
Average Maximum
FUN 81 (s)
DER
ERR
SD
V
C
* (IOREF (s))
↕
z
z
z
z
Instruction format
Number of steps
244
Condition
Steps
FUN 81 (s)
—
3
* (IOREF (s))
Bit
Word
Double word
Usable I/O
X
Y
R,
M
TD, SS,
CU, CT
WX WY
WR,
WM TC DX DY
DR,
DM
C
o
nstant
Other
s
Type
{
Function
s
Input type
H00: Input refresh
H01: Output refresh
• Depending on the I/O type of the area specified by s, refresh is performed with respect to I/O modules only, output modules
only.
• Refresh is performed by each slot assignment according to the I/O assignment.
• If the refresh processing is completed normally, DER is set to '0.'
* ( ) indicates the display when the Ladder Editor is used.
Notes
• If the I/O type is other than H00 or H01, DER is set to “1” and no processing will be performed.
• If the argument s exceeds the maximum I/O number, DER is set to “1” and no processing will be performed.
Program example
R000
LD
R000
AND
DIF0
[
WR0004 = 0
FUN 81 (WR0004)
]
LD
R001
AND
DIF1
[
WR0004 = 1
FUN 81 (WR0004)
]
R001
DIF1
WR0004 = 0
FUN 81 (WR0004 )
DIF0
WR0004 = 1
FUN 81 (WR0004 )
Program description
• Upon leading of R000, the input module is refreshed.
• Upon leading of R001, the output module is refreshed.
F