Oper at ions and monit o ring, Multi-speed select – Hitachi L100 User Manual
Page 98
L100 Inverter
Oper
at
ions
and Monit
o
ring
4–7
Multi-Speed Select
The inverter provides storage parameters for up to
16 different target frequencies (speeds) that the
motor output uses for steady-state run condition.
These speeds are accessible through programming
four of the intelligent terminals as binary-encoded
inputs CF1 to CF4 per the table below. These can
be any of the five inputs, and in any order. You can
use fewer inputs if you need eight or less speeds.
Note: When choosing a subset of speeds to use,
always start at the top of the table, and with the
least-significant bit: CF1, CF2, etc.
The figure below shows how input switches config-
ured with CF1 functions can change the motor
speed in real time.
.
NOTE: Speed 1 is set by the A01
parameter value.
Multi-
speed
Input Function
CF4
CF3
CF2
CF1
Speed 1
0
0
0
0
Speed 2
0
0
0
1
Speed 3
0
0
1
0
Speed 4
0
0
1
1
Speed 5
0
1
0
0
Speed 6
0
1
0
1
Speed 7
0
1
1
0
Speed 8
0
1
1
1
Speed 9
1
0
0
0
Speed 10
1
0
0
1
Speed 11
1
0
1
0
Speed 12
1
0
1
1
Speed 13
1
1
0
0
Speed 14
1
1
0
1
Speed 15
1
1
1
0
Speed 16
1
1
1
1
1st
time
CF1
CF2
CF3
2nd
3rd
7th
6th
5th
4th
8th
Speed
Switches
Fwd Run
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
02
CF1
Multi-speed select,
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
03
CF2
Multi-speed select,
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
04
CF3
Multi-speed select,
Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
05
CF4
Multi-speed select,
Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0