“A” Group: Standard Functions

Conf

igur

in

g

Dr

iv

e P

a

ra

m

e

ter

s

3–20

NOTE: For A95 and A96, if you set a very rapid Acc1 or Dec1 time (less than 1.0
second), the inverter may not be able to change rates to Acc2 or Dec2 before reaching
the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in order
to achieve the second ramp to the target frequency.

A96

Dec1 to Dec2
frequency transition
point

Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz

0.0

Hz

F-07

DEC
CHFr

A97

Acceleration curve
selection

Set the characteristic curve of
Acc1 and Acc2, two options:
00 ...linear
01 ...S-curve

00

F-06

ACC
LINE

A98

Deceleration curve
setting

Set the characteristic curve of
Acc1 and Acc2, two options:
00 ...linear
01 ...S-curve

00

F-07

DEC
LINE