Monitoring Trip Events, History, & Conditions

T

roub

le

shoot

in

g

and Maint

enance

6–6

Error Codes

An error code will appear on the display automatically when a fault causes the inverter to
trip. The following table lists the cause associated with the error.

Error
Code

Name

Cause(s)

E01

Over current event while
at constant speed

The inverter output was short-circuited, or the motor
shaft is locked or has a heavy load. These conditions
cause excessive current for the inverter, so the inverter
output is turned off.

E02

Over current event during
deceleration

E03

Over current event during
acceleration

E04

Over current event while
motor is stopped

E05

Overload protection

When a motor overload is detected by the electronic
thermal function, the inverter trips and turns off its
output.

E07

Over voltage protection

When the DC bus voltage exceeds a threshold, due to
regenerative energy from the motor.

E08

EEPROM error

When the built-in EEPROM memory has problems
due to noise or excessive temperature, the inverter
trips and turns off its output to the motor.

E09

Under-voltage error

A decrease of internal DC bus voltage below a thresh-
old results in a control circuit fault. This condition
can also generate excessive motor heat or cause low
torque. The inverter trips and turns off its output.

E11

E22

CPU error

A malfunction in the built-in CPU has occurred, so
the inverter trips and turns off its output to the motor.

E12

External trip

A signal on an intelligent input terminal configured as
EXT has occurred. The inverter trips and turns off the
output to the motor.

E13

USP

When the Unattended Start Protection (USP) is
enabled, an error occurred when power is cycled
while the inverter is in Run Mode. The inverter trips
and does not go into Run Mode until the error is
cleared.

E14

Ground fault

The inverter is protected by the detection of ground
faults between the inverter output and the motor upon
during powerup tests. This feature protects the
inverter, and does not protect humans.

E15

Input over-voltage

When the input voltage is higher than the specified
value, it is detected 100 seconds after powerup and
the inverter trips and turns off its output.

E21

Inverter thermal trip

When the inverter internal temperature is higher than
the specified value, the thermal sensor in the inverter
module detects the higher temperature of the power
devices and trips, turning the inverter output off.