Frequency-related Functions

The inverter output generates a variable-frequency waveform that determines the motor
speed (minus slip losses). You can configure the lower frequency limit to be greater than
zero as shown in the graph (below left). The upper limit must not exceed the rating of the
motor or capability of the machinery. Some motors or machines exhibit resonances at a
particular speed, which can be destructive. The inverter has up to three jump frequencies
(see graph, below right) with hysteresis around them to cause the inverter output to skip
around the sensitive frequency values.

Output frequency

A62

A61 Upper

limit

Frequency command

Lower

limit

Settable

range

Output frequency

A64

A63

Frequency command

Jump

frequency

“A” Function

Run-

time
Edit

Defaults

DOP,DRW,DOP+

Func.

Code

Name

Description

EU/

US

Units

Func.

Code

Name

A61

Frequency upper limit
setting

Sets a limit on output
frequency less than the
maximum frequency (A04)
Range is 0.5 to 360.0 Hz
0.0 ..setting is disabled
>0.1 setting is enabled

0.0

Hz

F-26

LIMIT H

A62

Frequency lower limit
setting

Sets a limit on output
frequency greater than zero
Range is 0.5 to 360.0 Hz
0.0 ..setting is disabled
>0.1 setting is enabled

0.0

Hz

F-26

LIMIT L

A63,
A65,
A67

Jump (center)
frequency setting

Up to 3 output frequencies can
be defined for the output to
jump past to avoid motor
resonances (center frequency)
Range is 0.0 to 360.0 Hz

0.0
0.0
0.0

Hz

F-27

JUMP F1
JUMP F2
JUMP F3

A64,
A66,
A68

Jump (hysteresis)
frequency width
setting

Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz

0.5
0.5
0.5

Hz

F-27

JUMP W1
JUMP W2
JUMP W3