Free-run Stop

When the terminal [FRS] is turned on, the inverter stops the output and the motor enters
the free-run state (coasting). If terminal [FRS] is turned off, the output resumes sending
power to the motor if the Run command is still active. The free-run stop feature works
with other parameters to provide flexibility in stopping and starting motor rotation.

In the figure below, parameter B88 selects whether the inverter resumes operation from
0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS]
terminal turns off. The application determines which is the best setting.

Parameter B03 specifies a delay time before resuming operation from a free-run stop. To
disable this feature, use a zero delay time.

time

FRS

Switches

Motor

speed

FW, RV

(Run)

Zero-frequency start

B88 = 00

time

FRS

Switches

Motor

speed

FW, RV

(Run)

Resume from motor speed

B88 = 01

B03 wait time

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

11

FRS

Free-run Stop

ON

Causes output to turn off, allowing motor to free
run (coast) to stop

OFF

Output operates normally, so controlled deceler-
ation stops motor

Valid for inputs:

C01, C02, C03, C04, C05

Required settings:

B03, B88, C11 to C15

Notes:

When you want the [FRS] terminal to be active low
(normally closed logic), change the setting (C11 to
C15) which corresponds to the input (C01 to C05)
that is assigned the [FRS] function.

Example:

FW FRS

See I/O specs on page 4–5.