PID Loop Operation

In standard operation, the inverter uses a reference source selected by parameter A01 for
the output frequency, which may be a fixed value (F01), a variable set by the front panel
potentiometer, or value from an analog input (voltage or current). To enable PID opera-
tion, set A71 = 01. This causes the inverter to calculate the target frequency, or setpoint.

A calculated target frequency can have a lot of advantages. It lets the inverter adjust the
motor speed to optimize some other process of interest, while saving energy as well.
Refer to the figure below. The motor has some eventual effect on a process of interest. To
control the external process, the inverter must monitor the process variable. This requires
wiring a sensor to either the analog input terminal O (voltage) or terminal OI (current).

When enabled, the PID loop calculates the ideal output frequency to minimize the loop
error. This means we no longer command the inverter to run at a particular frequency, but
we specify the ideal value for the process variable. That ideal value is called the setpoint,
and is specified in the units of the external process variable. For a pump application it
may be gallons/minute, or it could be air velocity or temperature for an HVAC unit.
Parameter A75 is a scale factor that relates the external process variable units to motor
frequency. The figure below is a more detailed diagram of the PID function.

Motor

Inverter

Process

Sensor

Process Variable (PV)

Setpoint

Error

PID

Calculation

Freq.

PV

External

SP

Monitor

P gain

A75

A11

F01

A76

A72

A15

A01

I gain

A73

D gain

A74

A75

D04

A12

A13 A14

Analog input scaling

Voltage

O

OI

L

Current

A GND

PID V/I

input select

Process Variable

(Feedback)

Scale factor

Frequency

setting

F01

Scale factor

Setpoint

(Target)

1/A75

Scale factor

reciprocal

Multi-speed

settings

Standard

setting

A20 to A35

Frequency

source select

Potentiometer

on keypad

Error

[AT]

V/I input

select

PV

SP