Analog Input Settings

The inverter has the capability to accept an external analog input that can command the
output frequency to the motor. Voltage input (0 –10V) and current input (4–20mA) are
available on separate terminals (“O” and “OI,” respectively). The analog input settings
add scaling and offset adjustments between the analog input and the frequency output.

In the graph below (left), A13 and A14 select the active portion of the input voltage or
current range. The parameters A11 and A12 select the start and end frequency of the
converted output frequency range, respectively. Together, these four parameters define a
line segment as shown (below, right). When the line does not begin at the origin, A15
defines whether the inverter outputs 0Hz or the A11frequency when the analog input
value is less than the A13 setting (determines the non-linear part of the translation).

Frequency

10V

20mA

A13

A14

0V

4mA

A11

A12

A15 = 00

A15 = 01

Frequency

% input

scale

10V

20mA

A13

A14

0V

4mA

A11

A12

% input

scale

0 Hz

“A” Function

Run-

time
Edit

Defaults

DOP,DRW,DOP+

Func.

Code

Name

Description

EU/

US

Units

Func.

Code

Name

A11

External frequency
output zero reference

The output frequency corre-
sponding to the analog input
range starting point

0

Hz

F-31

IN EXS

A12

External frequency
output span reference

The output frequency corre-
sponding to the analog input
range ending point

0

Hz

F-31

IN EXE

A13

External frequency
input bias start

The starting point (offset) for
the active analog input range

0

%

F-31

IN EX%S

A14

External frequency
input bias end

The ending point (offset) for
the active analog input range

100

%

F-31

IN EX%E

A15

External frequency
offset enable

Two options; select codes:
00... Use offset (A11 value)
01... Use 0 Hz

01

F-31

IN
LEVEL

A16

External frequency
filter time constant

Range n = 1 to 8, where n =
number of samples for avg.

8

Sam-

ples

F-31

IN
F-SAMP