PID Control

When enabled, the built-in PID loop calculates an ideal inverter output value to cause a
loop feedback process variable (PV) to move closer in value to the setpoint (SP). The
current frequency command serves as the SP. The PID loop calculations will read the
analog input for the process variable (you specify the current or voltage input) and calcu-
late the output. A scale factor in A75 lets you multiply the PV by a factor, converting it
into engineering units for the process. Proportional, integral, and derivative gains are all
adjustable. See page 4–27 for more information on PID loop control.

NOTE: The setting A73 for the integrator is the integrator’s time constant Ti, not the
gain. The integrator gain Ki = 1/Ti. When you set A73 = 0, the integrator is disabled.

“A” Function

Run-

time
Edit

Defaults

DOP,DRW,DOP+

Func.

Code

Name

Description

EU/

US

Units

Func.

Code

Name

A71

PID Function Enable

Enables PID function,
two option codes:
00... PID Disable
01... PID Enable

00

F-43

PID SW

A72

PID proportional gain Proportional gain has a range

of 0.2 to 5.0

1.0

F-43

PID P

A73

PID integral time
constant

Integral time constant has a
range of 0.0 to 150 seconds

1.0

sec.

F-43

PID I

A74

PID derivative gain

Derivative gain has a range of
0.0 to 100 seconds

0.0

sec.

F-43

PID D

A75

PV scale conversion

Process Variable (PV) scale
factor (multiplier), range of
0.01 to 99.99

1.0

F-43

PID
CONV

A76

PV source setting

Selects source of Process
Variable (PV), option codes:
00... “OI” terminal (current in)
01... “O” terminal (voltage in)

00

F-43

PID INPT