Oper at ions and monit o ring – Hitachi L100 User Manual

Page 114

background image

L100 Inverter

Oper

at

ions

and Monit

o

ring

4–23

The alarm output terminals are connected as shown below (left) by default, or after
initialization. The contact logic can be inverted as shown (below right) by using the
parameter setting C33. The relay contacts normally open (N.O.) and normally closed
(N.O.) convention uses “normal” to mean the inverter has power and is in Run or Stop
Mode. The relay contacts switch to the opposite position when it is in Trip Mode or
when input power is Off.

N.C. contacts (after initialization)

N.O. contact (inverted by C33 setting)

During normal running

When an alarm occurs

or power is turned off

During normal running

or power is turned off

When an alarm occurs

AL0 AL1 AL2

AL0 AL1 AL2

AL0 AL1 AL2

AL0 AL1 AL2

Contact

Power

Run

State

AL0-

AL1

AL0-

AL2

N.C.

(after

initialize,

C33=01)

ON

Normal

Closed

Open

ON

Trip

Open

Closed

OFF

Open

Closed

Contact

Power

Run

State

AL0-

AL1

AL0-

AL2

N.O.

(set

C33=00)

ON

Normal

Open

Closed

ON

Trip

Closed

Open

OFF

Open

Closed