Oper at ions and monit o ring – Hitachi L100 User Manual
Page 114
L100 Inverter
Oper
at
ions
and Monit
o
ring
4–23
The alarm output terminals are connected as shown below (left) by default, or after
initialization. The contact logic can be inverted as shown (below right) by using the
parameter setting C33. The relay contacts normally open (N.O.) and normally closed
(N.O.) convention uses “normal” to mean the inverter has power and is in Run or Stop
Mode. The relay contacts switch to the opposite position when it is in Trip Mode or
when input power is Off.
N.C. contacts (after initialization)
N.O. contact (inverted by C33 setting)
During normal running
When an alarm occurs
or power is turned off
During normal running
or power is turned off
When an alarm occurs
AL0 AL1 AL2
AL0 AL1 AL2
AL0 AL1 AL2
AL0 AL1 AL2
Contact
Power
Run
State
AL0-
AL1
AL0-
AL2
N.C.
(after
initialize,
C33=01)
ON
Normal
Closed
Open
ON
Trip
Open
Closed
OFF
–
Open
Closed
Contact
Power
Run
State
AL0-
AL1
AL0-
AL2
N.O.
(set
C33=00)
ON
Normal
Open
Closed
ON
Trip
Closed
Open
OFF
–
Open
Closed