Set the READ/WRITE parameter to READ. The gateway supports a TARGET
DEVICE
parameter value of 500CPU or PLC5. In order to complete the
configuration of the MSG instruction, select the SETUP SCREEN area of the
MSG object. This displays the following dialog box.

The TARGET DEVICE DATA TABLE ADDRESS must be set to a valid file
element (such as, N11:0) for SLC and PLC5 messages. The MULTIHOP option
must be set to YES.

Fill in the MULTIHOP tab portion of the dialog box as shown in the following
illustration.

Set the IP address value to the gateway’s Ethernet IP address. The "Insert" key
must be pressed to add the second line for ControlLogix Backplane and set the
slot number to zero.