Preset Multiple Registers (Function Code 16)
Query
Holding registers existing within the controller can have their contents changed
by this message (a maximum of 125 registers). However, because the controller
is actively scanning, it also can alter the content of any holding register at any
time. The values are provided in binary up to the maximum capacity of the
controller (16-bit for the 184/384 and 584); unused high order bits must be set to
zero.
Note: Function codes 5, 6, 15, and 16 are the only messages that will be recognized as valid for
broadcast.
Adr
Func
Hi
Add
Lo Add
Quantity
Byte
Cnt
Hi
Data
Lo
Data
Hi
Data
Lo Data Error Check
Field
11
10
00
87
00
02 04
00
0A
01
02
CRC
Response
The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.
Adr
Func
Hi Addr
Lo Addr
Quantity
Error Check Field
11
10
00
87
00
02
56