ProSoft Technology PLX31-EIP-SIE User Manual

Page 144

background image

MBS Protocol

PLX3x Series

User Manual

Ethernet and Serial Gateways

Page 144 of 218

ProSoft Technology, Inc.

September 17, 2014

Response
The normal response to the Command Request is to re-transmit the message as
received after the coil state has been altered.

Adr

Func

Data Coil # Hi

Data Coil # Lo

Data On/ Off

Data

Error Check Field

11

05

00

AC

FF

00

CRC

The forcing of a coil via MODBUS function 5 will be accomplished regardless of
whether the addressed coil is disabled or not (In ProSoft products, the coil is only
affected if the necessary ladder logic is implemented).

Note: The Modbus protocol does not include standard functions for testing or changing the

DISABLE state of discrete inputs or outputs. Where applicable, this may be accomplished via
device specific Program commands (In ProSoft products, this is only accomplished through ladder

logic programming).

Coils that are reprogrammed in the controller logic program are not automatically
cleared upon power up. Thus, if such a coil is set ON by function Code 5 and
(even months later), an output is connected to that coil, the output will be "hot".

Preset Single Register (Function Code 06)

Query
Function (06) allows the user to modify the contents of a holding register. Any
holding register that exists within the controller can have its contents changed by
this message. However, because the controller is actively scanning, it also can
alter the content of any holding register at any time. The values are provided in
binary up to the maximum capacity of the controller unused high order bits must
be set to zero. When used with server address zero (Broadcast mode) all server
controllers will load the specified register with the contents specified.

Note Functions 5, 6, 15, and 16 are the only messages that will be recognized as valid for

broadcast.

Adr

Func

Data Start Reg
Hi

Data Start Reg
Lo

Data #of Regs Hi Data #of Regs Lo Error Check Field

11

06

00

01

00

03

CRC