Sie diagnostics – ProSoft Technology PLX31-EIP-SIE User Manual
Page 181
PLX3x Series
SIE Protocol
Ethernet and Serial Gateways
User Manual
ProSoft Technology, Inc.
Page 181 of 218
September 17, 2014
9.3
SIE Diagnostics
The best way to troubleshoot the SIE driver is to use ProSoft Configuration
Builder to access the diagnostic capabilities of the gateway through the Ethernet
debug port. For instructions on how to access Diagnostics, see
Diagnostics in ProSoft Configuration Builder
(page 36).
9.3.1 Client Command Errors
Each SIE Client has an associated status data area located in the
gateway’s
upper memory. The Data Map functionality of the gateway can be used to map
this data into the normal user data range of the gateway
(page 25).
The following table lists the starting addresses in upper memory where the status
data for each Client can be found.
Client
Gateway Starting Register for Status Data
0
21100
1
21125
2
21151
…
…
…
…
18
21568
19
21594
The following table describes the content of each Client’s status data area.
Word Offset
Description
0
Command Request Count
1
Command Response Count
2
Command Error Count
3
Number of Request Packets
4
Number of Response Packets
5
Errors Sent
6
Errors Received
7
Configuration Error Word
8
Current Error
9
Last Error
10 to 25
Command List Errors (16 per Client)
For every command that has an error, the gateway automatically sets the poll
delay parameter to 30 seconds. This instructs the gateway to wait 30 seconds
before it attempts to issue the command again.