ProSoft Technology PLX31-EIP-SIE User Manual

Page 136

background image

MBS Protocol

PLX3x Series

User Manual

Ethernet and Serial Gateways

Page 136 of 218

ProSoft Technology, Inc.

September 17, 2014

Master Port: Modbus Slave List Status

Slave List Status values for each Master port are returned to the address
locations specified in the following table.

Modbus Port

Address Range

1

4510 to 4764

2*

4910 to 5164

3*

5310 to 5564

4*

5710 to 5964

*Status data for Ports 2 through 4 is only present in 4-port MBS gateways.

Port 1 Slave List Status Layout
The addresses listed are for Port 1 only; but the format is the same for each port.
The start address for each port is given in the previous section.

Internal
Database
Address
(Example)

Offset

Description

4510

0

Slave #1 Status

4511

1

Slave #2 Status

4512

2

Slave #3 Status

4513

3

Slave #4 Status

4514

4

Slave #5 Status

.

.

.

.

The slave status list contains the current poll status of each slave device on a
Master port. Slaves attached to a Master port can have one of three states.

0

The slave has not defined in the command list for the Master port and will not be polled
from the Command List.

1

The slave is configured to be polled by the Master port and the most recent
communication attempt was successful.

2

The Master port has failed to communicate with the slave device. Communication with
the slave is suspended for a user defined period based on the scanning of the
command list.

Slaves are defined to the system when the gateway loads the Master Command
List during start-up and initialization. Each slave defined will be set to a state
value of 1 in this initial step. If the Master port fails to communicate with a slave
device (timeout expired on a command, retries failed), the Master will set the
state of the slave to a value of 2 in this status table. This suspends
communication with the slave device for a user-specified Error Delay Count.