Notes on Addressing in S7 Processors

S7-300/S7-1200 Processor:

Byte Address in Data Block:

DB1.DBB1 DB1.DBB3

2#0000_0110 2#0000_0000 2#0110_0001 2#0011_0110 2#1100_0110

DB1.DBB0

DB1.DBB2

DB1.DBB4

Word Address in Data Block:

DB1.DBW1 DB1.DBW3

2#0000_0110 2#0000_0000 2#0110_0001 2#0011_0110 2#1100_0110

DB1.DBW0 DB1.DBW2

The gray area above represents the byte memory locations being overlapped
when word address is used consecutively (DB1.DBW0, DB1.DBW1, DB1.DBW2,
etc).

If DB1.DBW0 is used as the first address in the Siemens processor, the next
word address that can be used without overwriting the data would be
DB1.DBW2.

Double Word Address in Data Block:

DB1.DBD1

2#0000_0110 2#0000_0000 2#0110_0001 2#0011_0110 2#1100_0110

DB1.DBD0

The gray area above represents the byte memory locations being overlapped
when double word address is used consecutively (DB1.DBD0, DB1.DBD1,
DB1.DBD2, etc).