Parameter

Value

Description

only if the Float Flag is set to YES.
For example, if the Float Offset value is set to 3000 and the
Float Start parameter is set to 7000, the data returned as
floating-point data for register 47001 (or 407001) will actually
come from internal gateway registers 3000 and 3001. If the
requested address was 47002 (407002), the data will be
returned from internal registers 3002 and 3003. If the requested
address was 47101 (407101), the data will be returned from
internal registers 3200 and 3201; and so on.

ARP Timeout

1 to 60

This parameter specifies the number of seconds to wait for an
ARP reply after a request is issued.

Command
Error Delay

0 to 300

This parameter specifies the number of 100 millisecond
intervals to turn off a command in the error list after an error is
recognized for the command. If this parameter is set to 0, there
will be no delay.