8.1

ASCII Functional Overview

The ASCII protocol permits the PLX3x Gateway to interface any ASCII device to
the many protocols and networks available. ASCII devices include barcode
scanners, weigh scales, many field instruments, printers, and terminals. The
protocol supports one to four serial communication ports that provide
accessibility from one to four independent serial networks.


8.1.1 General Specifications

Ports: One to four serial communication ports to receive and/or transmit

data

Receive buffer size: 255 bytes

Receive termination: Stream mode, termination character(s), message

timeout, inter-character delay, or packet size length

Receive database location: -1 = disable receiver, 0 to 3896

Transmit buffer size: 255 bytes

Transmit characters with pacing: 0 to 65535 millisecond delay between

each transmitted character

Transmit database location: -1 = disable transmitter, 0 to 3896

Communication Configuration

o Baud Rate: 110 to 115,200
o Parity: None, Odd, Even
o Data Bits: 5 to 8
o Stop Bits: 1 or 2
o RTS On and Off Timing: 0 to 65535 milliseconds
o Minimum Response Delay: 0 to 65535 milliseconds
o Hardware or Software Handshaking: RTS/CTS, DTR/DSR, or

XON/XOFF