beautypg.com

Eip error codes – ProSoft Technology PLX31-EIP-SIE User Manual

Page 73

background image

PLX3x Series

EIP Protocol

Ethernet and Serial Gateways

User Manual

ProSoft Technology, Inc.

Page 73 of 218

September 17, 2014

5.3.3 EIP Error Codes

The gateway error codes are listed in this section. Error codes returned from the
command list process are stored in the command list error memory region. A
word is allocated for each command in the memory area. The error codes are
formatted in the word as follows: The least-significant byte of the word contains
the extended status code and the most-significant byte contains the status code.

Use the error codes returned for each command in the list to determine the
success or failure of the command. If the command fails, use the error code to
determine the cause of failure.

Note: The gateway specific error codes (not EtherNet/IP/PCCC compliant) are returned from within

the gateway and never returned from an attached EtherNet/IP/PCCC slave device. These are error

codes that are part of the EtherNet/IP/PCCC protocol or are extended codes unique to this
gateway. The most common errors for the EtherNet/IP/PCCC protocol are shown in the following

tables:

Local STS Error Codes

Code (Int)

Code (Hex) Description

0

0x0000

Success, no error

256

0x0100

DST node is out of buffer space

512

0x0200

Cannot guarantee delivery (Link Layer)

768

0x0300

Duplicate token holder detected

1024

0x0400

Local port is disconnected

1280

0x0500

Application layer timed out waiting for response

1536

0x0600

Duplicate node detected

1792

0x0700

Station is offline

2048

0x0800

Hardware fault